Output
Output Power Capacity 500 Watts / 750 VA
Max Configurable Power 500 Watts / 750 VA
Nominal Output Voltage 120V
Output Voltage Distortion Less than 5% at full load
Output Frequency (sync to mains) 47 - 53 Hz for 50 Hz nominal, 57 - 63 Hz for 60 Hz nominal
Topology Line Interactive
Waveform Type Sine wave
Output Connections
(6) NEMA 5-15R NEMA 5-15R
Input
Nominal Input Voltage 120V
Input Frequency 50/60 Hz +/- 3 Hz (auto sensing)
Input Connections
NEMA 5-15P NEMA 5-15P
Cord Length 1.83 meters
Input voltage range for main operations 82 - 144V
Input voltage adjustable range for mains operation 75 - 154V
Batteries amp; Runtime
Battery Type Maintenance-free sealed Lead-Acid battery with suspended electrolyte : leakproof
Typical recharge time 3 hour(s)
Replacement Battery RBC48
RBC⢠Quantity 1
Runtime Graph
Hover over the line on the graph above to view the runtime at any desired load
Curve fit to measured runtime data. All measurements taken with new, fully charged batteries, at typical environmental conditions, with no electrical input and balanced resistive load (PF = 1.0) output.
View Enlarged Graph View Runtime Chart
Energy Use/Efficiency
Load Efficiency
25% 89.4%
50% 94.1%
75% 95.6%
100% 96.3%
Hover over the line on the graph above to view the efficiency at any desired load
Curve fit to measured efficiency data. All measurements taken in normal operating mode, at typical environmental conditions, with nominal electrical input and balanced resistive load (PF = 1.0) output.
View Enlarged Graph
Communications amp; Management
Interface Port(s) DB-9 RS-232, Smart-Slot, USB
Available SmartSlot⢠Interface Quantity 1
Control panel LED status display with load and battery bar-graphs and On Line : On Battery : Replace Battery : and Overload Indicators
Audible Alarm Alarm when on battery : distinctive low battery alarm : configurable delays
Emergency Power Off (EPO) Optional
Surge Protection and Filtering
Surge energy rating 540 Joules
Filtering Full time multi-pole noise filtering : 0.3% IEEE surge let-through : zero clamping response time : meets UL 1449
Physical
Maximum Height 157.00 mm
Maximum Width 137.00 mm
Maximum Depth 358.00 mm
Net Weight 13.18 KG
Shipping Weight 14.55 KG
Shipping Height 290.00 mm
Shipping Width 270.00 mm
Shipping Depth 500.00 mm
Color Black
Units per Pallet 24.00
Environmental
Operating Environment 0 - 40 °C
Operating Relative Humidity 0 - 95%
Operating Elevation 0-3000 meters
Storage Temperature -15 - 45 °C
Storage Relative Humidity 0 - 95%
Storage Elevation 0-15000 meters
Audible noise at 1 meter from surface of unit 40.00 dBA
Online Thermal Dissipation 90.00 BTU/hr
Conformance
Regulatory Approvals BSMI, CSA, FCC Part 15 Class A, UL 1778, UL Listed, VCCI
Standard Warranty 2 years repair or replace
Sustainable Offer Status
RoHS Compliant
REACH REACH: Contains No SVHCs
Other Environmental Compliance China RoHS